Thirty per cent of plumbers fail these audits and inspections.

Where appropriate, BPC staff provide onsite guidance and education to help plumbers comply with rules and regulations. However, serious non-compliances may be referred for further investigation or enforcement action.

In FY 2025-26, the BPC:

  • completed 5200+ compliance audits and drainage inspections
  • issued 900+ rectification notices to fix non-compliant work
  • issued 150 infringement notices.

Read on to see what our inspectors found.

Drainage inspections

  • 2400+ drainage inspections carried out across Victoria
  • 29% of drainage inspections failed
    • 12% failed due to non-compliance
    • 17% failed because they were not ready for inspection.

Top compliance problems

  • Drain failed the air test
  • Bends formed risers and below-ground traps did not have the required concrete support
  • Drain did not have appropriate bedding/support
  • Drain not laid straight with even grade
  • 100mm junctions from branch drains to main drain were not inclined at least 15°.

Compliance audits

  • 1800+ plumbing compliance audits completed
  • 31% of plumbing compliance audits failed.

Top compliance problems

  • Multilayer gas lines did not have appropriate fire emergency shut-off isolation
  • Failure to meet minimum clearances between rangehoods and gas cooking surfaces
  • Dissimilar metals between roof sheets and ductwork in direct contact
  • Hot water not tempered to maximum 50° C where required
  • Hot water pressure relief drains not discharging appropriately
  • Above-ground drains not supported appropriately
  • Water pressure at interior outlets exceeds 500kPa.

Heat pump installs

  • 120,000+ air-conditioning compliance certificates issued
  • 200+ targeted audits completed
  • 22% of audited installations failed.

Top compliance problems

  • Non-compliant termination of condensation drain
  • Insufficient access to roof-mounted units
  • Insufficient access and lighting to units installed in roof spaces
  • Refrigerated air-conditioning pipework not supported/clipped appropriately
  • Refrigerated air-conditioning pipework insulation unprotected from UV.

Gasfitting

Gasfitting work accounted for 11% of all non-compliances identified during compliance audits.

Top compliance problems

  • Multilayer gas pipe missing fire emergency isolation
  • Multilayer gas pipe installed above ground and external to building
  • Gas appliances not commissioned correctly
  • Gas cooking appliance combustible surfaces unprotected
  • Proprietary gas systems missing gas labels
  • Missing 1m metallic pipework into wall from appliance point
  • Consumer piping ends unsealed during install
  • Inappropriate use of PVC or PE gas pipe.

Learn more about our plumbing audit and inspection program.