Thirty per cent of plumbers fail these audits and inspections.
Where appropriate, BPC staff provide onsite guidance and education to help plumbers comply with rules and regulations. However, serious non-compliances may be referred for further investigation or enforcement action.
In FY 2025-26, the BPC:
- completed 5200+ compliance audits and drainage inspections
- issued 900+ rectification notices to fix non-compliant work
- issued 150 infringement notices.
Read on to see what our inspectors found.
Drainage inspections
- 2400+ drainage inspections carried out across Victoria
- 29% of drainage inspections failed
- 12% failed due to non-compliance
- 17% failed because they were not ready for inspection.
Top compliance problems
- Drain failed the air test
- Bends formed risers and below-ground traps did not have the required concrete support
- Drain did not have appropriate bedding/support
- Drain not laid straight with even grade
- 100mm junctions from branch drains to main drain were not inclined at least 15°.
Compliance audits
- 1800+ plumbing compliance audits completed
- 31% of plumbing compliance audits failed.
Top compliance problems
- Multilayer gas lines did not have appropriate fire emergency shut-off isolation
- Failure to meet minimum clearances between rangehoods and gas cooking surfaces
- Dissimilar metals between roof sheets and ductwork in direct contact
- Hot water not tempered to maximum 50° C where required
- Hot water pressure relief drains not discharging appropriately
- Above-ground drains not supported appropriately
- Water pressure at interior outlets exceeds 500kPa.
Heat pump installs
- 120,000+ air-conditioning compliance certificates issued
- 200+ targeted audits completed
- 22% of audited installations failed.
Top compliance problems
- Non-compliant termination of condensation drain
- Insufficient access to roof-mounted units
- Insufficient access and lighting to units installed in roof spaces
- Refrigerated air-conditioning pipework not supported/clipped appropriately
- Refrigerated air-conditioning pipework insulation unprotected from UV.
Gasfitting
Gasfitting work accounted for 11% of all non-compliances identified during compliance audits.
Top compliance problems
- Multilayer gas pipe missing fire emergency isolation
- Multilayer gas pipe installed above ground and external to building
- Gas appliances not commissioned correctly
- Gas cooking appliance combustible surfaces unprotected
- Proprietary gas systems missing gas labels
- Missing 1m metallic pipework into wall from appliance point
- Consumer piping ends unsealed during install
- Inappropriate use of PVC or PE gas pipe.
Learn more about our plumbing audit and inspection program.