Go to BPC Homepage Go to BPC Homepage

Log in

CW 03 Maximum static water pressure within a building

Plumbing Practice Note

Abbreviations and definitions

Purpose

The purpose of this Practice Note is to provide plumbing practitioners and homeowners with guidance on the regulatory requirements for water pressure within a property, and to outline the measures that could be taken to ensure compliance with Regulation in the NCC and relevant Australian Standards.

The content below provides guidance on:

  • Maximum static pressure and testing
  • Responsibilities as a Practitioner
  • Types of pressure regulating devices
  • Minimum Flow rate requirements
  • Complying with flow rate requirements

For guidance on the plumbing regulatory framework refer to Plumbing Practice Note RF-01 | Regulatory Framework 

Watch this short video

Maximum static pressure and testing

Under the Victorian Plumbing Regulations 2018, plumbing work must comply with the Plumbing Code of Australia (PCA) NCC Volume 3.

The maximum static pressure at any outlet (point of discharge) within a building must not exceed 500 kPa (except at fire service outlets). This applies to all new and altered plumbing work for cold and hot water.

The PCA specifies NCC clauses: Cold water (B1P5) and Heated water (B2P9) services and relevant performance requirements, as the maximum pressure at the point of discharge must be 500 kPa (except at fire service outlets).

Pressures exceeding 500 kPa can result in water hammer, reduce the service life of appliances, taps, fittings, and cause excessive noise within the system.

A practical way to determine the maximum static pressure is to connect a calibrated pressure gauge to the meter outlet located at the property boundary or the adjacent garden tap if installed. This will indicate the static pressure supplied by the water authority. If the measured pressure exceeds 500 kPa, a pressure-limiting and or pressure reduction valve must be installed.

Please note that kPa pressures are subject to fluctuation, and the recorded measurement represents the static pressure at the time the licensed plumber conducted the test. 

Responsibilities as a Practitioner

The plumbing practitioner has a responsibility to inform the homeowner if the pressure exceeds 500kPa and to advise that a pressure limiting and or pressure reduction valve is required in accordance with the Plumbing Regulations and NCC volume 3 (Plumbing Code of Australia).

The plumber should maintain clear documentation and records of all works carried out  and any recommendations made to the homeowner including details of any pressure readings recorded 

Types of pressure regulating devices

All pressure limiting valves and pressure reducing valves must be suitable for their intended purpose, comply with the applicable material and plumbing product requirements in accordance with the NCC.

Any product intended for use in contact with drinking water must comply with AS/NZS4020 or hold a WaterMark Licence issued in accordance with the relevant requirements.

Pressure limiting and pressure reduction valves may be installed at any location within the supply line, provided they remain readily accessible for inspection, adjusting, maintenance, and replacement.

Additional pressure reduction or limiting may be added to the heated water line if pressure exceeds the 500 kPa maximum.

Technical diagrams

The images below are indicative examples only and do not represent mandatory or approved installation locations. Pressure limiting or pressure reduction valves must be selected and located based on site-specific conditions. The final determination of device type, sizing, and location rests with the qualified plumber.

Right-angle pressure reducing valve after the meter

Right angle pressure reducing valve after the meter.

Figure 1: Right-angle PRV - 3500.1 

Straight pressure reducing valve after the Isolation valve

Straight pressure reducing valve after the isolation

Figure 2: Straight PRV 

Inline pressure limiting valve

Inline pressure limiting valve

Figure 3: Inline PLV 

Inline pressure reducing valve for heated water unit

Example of an inline pressure reducing valve for a Heated Water Unit 

Related documentation

  • Building Act 1993
  • Plumbing Regulations 2018
  • National Construction Code Volume Three (Plumbing code of Australia)
  • AS/NZS 3500.1 - Water services
  • AS/NZS 3500.4 – Heated water services
  • AS/NZS 4020
  • Watermark
  • ABCB

Contact us

If you have a technical enquiry, please email plumbingtechnicaladvice@bpc.vic.gov.au or call 1300 067 088.

Version history
Category
Cold water plumbing
This version
3.0
This version published
25 March 2026

Office of the State Building Surveyor

  • Print this page

Was this page helpful?
Your rating will help us improve our website.